SERIES E9000

Gas Feed Systems

Industrial Gas Feed for Chlorine, Sulfur Dioxide or Ammonia

Internal Switchover Mechanism

Hastelloy-C Inlet Valves

Solid Machined PVC Construction

 

Enchlor Inc. has been manufacturing the highest quality water treatment equipment and instrumentation since 1978. The Enchlor Inc. series E9000 gas feeders offer feed rate sizes from 4ppd to 500ppd. The Series E9000 offers multiple system configurations with internal automatic switchover, remote meters and cylinder or ton container mounting.

 

Construction

Enchlor Inc. continually strives to produce the longest lasting and most reliable gas chlorination and sulfonation equipment on the market. We believe that this means using only the highest quality materials and most rugged designs. Fine silver and Hastalloy rate vale and inlet valve components provide long life and accurate control. All body parts are machine from solid stock to provide the most durable chlorinator available

Internal Switchover

Each regulator is equipped with an internal switchover mechanism to automatically shift from standby to in-service upon depletion of the on-line cylinder. Each regulator has a status indicator to indicate standby or in-service operation. Each regulator incorporates a pressure relief (vent) valve with separate ports for gas feed and vent.

Economy

At last a high quality but economical chlorinator. Proof that quality and ?made in America' production does not need to be expensive.

Technical Data

Model Information Code

E9 þ¯ þ¯ þ¯ þ¯`

 

Gas
C - Chlorine
S - Sulfur Dioxide
A - Ammonia

Vacuum Regulator Mounting
5 - Two direct cylinder or manifold
mounted vacuum regulators,
and remote mounted meter panel
with rate valve
6 - Two direct Ton mounted vacuum regulators and remote mounted meter panel with rate valve

Available Gas Rotometers
3 - 4 ppd (75 g/h)
4 - 10 ppd (200 g/h)
5 - 25 ppd (0.5 kg/h)
6 - 50 ppd (0.9 kg/h)
7 - 100 ppd (2.0 kg/h)
8 - 250 ppd (5.0 kg/h)
9 - 500 ppd (10.0 kg/h)

Maximum Capacity
1 - 100ppd
2 - 250ppd
5 - 500ppd

Accuracy: within 4% of max rotometer capacity
Operating Range: 20:1, manual, 10:1 automatic
Back Pressure:
Maximum back pressure at point of application for a standard ejector is 140 psig. For pressures greater than 140 psig, consult factory.
Tubing Connections: 3/8" vacuum and vent
Operating Temperature: Ejector, 35¢ªF to 120¢ªF; Other components, -20¢ªF to 120¢ªF

The Series E9000 Gas Feeders can be installed a few feet to several hundred feet from the ejector depending on the maximum feed rate and the diameter of the vacuum tubing or piping.

Standard Installation and Spare Parts Kit (included with all of above models)
(10) ten #GAE-LED-111 lead gaskets
(1) one Ammonia bottle for checking connections
(2) two #ORE-VIT-121 nozzle gaskets
(1) one #GAE-VIT-122 ejector seat
(1) one #VRE-456-100 replacement filter
(1) one Operation and Maintenance Manual
*some internal parts have a Lifetime Warranty

NEW PRODUCTS!! 

SERIES 1100

AUTOVALVE

Look For Our Products In


Site Mailing List
Register with this site to receive email notifications, updates and new site information. Enter your email address and press the submit button.

Email Address:
*
Verify image below:
*



Enchlor, Inc.
130 West Main Street
Silverdale, PA 18962
Phone: 215 453-2533
Fax: 215 453-1101

Site Powered By
    WebBizBuilder Site Manager
    Online web site design