Technical Data
Model Information Code
Model 4 1
Gas
C - Chlorine
S - Sulfur Dioxide
Vacuum Regulator Mounting
1 - Direct cylinder or manifold mounted
with rate valve
3 - Direct cylinder or manifold mounted
with remote mounted meter panel
with rate valve
5 - Two direct cylinder or manifold
mounted vacuum regulators,
automatic switchover module,
and remote mounted meter panel
with rate valve
Available Gas Rotometers
3 - 4 ppd (75 g/h)
4 - 10 ppd (200 g/h)
5 - 25 ppd (0.5 kg/h)
6 - 50 ppd (0.9 kg/h)
7 - 100 ppd (2.0 kg/h)
Standard Supplied Equipment
with Each Available Model
25' (8m) 3/8" vacuum and vent tubing
(2) two vent outlet screens
(1) one Standard Installation and Spare Parts Kit
Accuracy: within 4% of max rotometer capacity
Operating Range: 20:1, manual, 10:1 automatic
Back Pressure: Maximum back pressure at point of
application for a standard ejector is 140 psig.
For pressures greater than 140 psig, consult factory.
Tubing Connections: 3/8" vacuum and vent Operating Temperature: Ejector, 35¢ªF to 120¢ªF;
Other components, -20¢ªF to 120¢ªF
|
Model
41__1C
(1) one vacuum regulator with gas rotometer, rate valve and chlorine supply indicator
(1) one ejector/diffuser assembly
25' (8m) 3/8" vacuum and vent tubing
(1) one vent outlet screen
(1) one Standard Installation and Spare Parts Kit
41__3C
(1) one vacuum regulator with gas rotometer and chlorine supply indicator (no rate valve)
(1) one remote mounted meter panel with
gas rotometer and rate valve
(1) one ejector/diffuser assembly
25' (8m) 3/8" vacuum and vent tubing
(1) one vent outlet screen
(1) one Standard Installation and Spare Parts Kit
41__5C
(2) two vacuum regulators with gas rotometers
and chlorine supply indicators (no rate valves)
(1) one automatic switchover module,
vacuum operated
(1) one remote mounted meter panel with
gas rotometer and rate valve
(1) one ejector/diffuser assembly
25' (8m) 3/8" vacuum and vent tubing
(1) one vent outlet screen
(1) one Standard Installation and Spare Parts Kit
Standard Installation and Spare Parts Kit (included with all of above models)
(10) ten #GA-LED-111 lead gaskets
(1) one Ammonia bottle for checking connections
(2) two #ORE-VIT-121 nozzle gaskets
(1) one #GAE-VIT-122 ejector seat
(1) one #VRE-456-100 replacement filter
(1) one Operation and Maintenance Manual
*some internal parts have a lifetime warranty |